ENC-AR1610HD
Thermal management of various outdoor control panel utility facilities.
Specifications
Mount Type Side-mount Cooling Capacity (W) 1450/1600 Setting Temperature Range (°C) 25 to 45 Use Area Temperature (°C) -5 to 55 Use Area Humidity (%RH) 10-85(No condensation) External Dimensions (mm) H1000×W400×D260 Volume (kg) 42 Surface Finish 180-HL No.4 NSSC finish Voltage Rating (V) Single-phase AC100 Consumption Current/Rating (A) 7.6/7.0 Consumption Current/MAX (A) 8.5/8.8 Starting Current (A) 22.3/20.5 Consumption Voltage/Rating (W) 610/650 Consumption Voltage/MAX (W) 740/830 Noise Resistance Fast Transient / LEVEL4 by burst immunity test Vibration Resistance Equivalent to JIS Z 0200 Level1 Dust & Water Protection Grade Equivalent to IP54 (internal circulation route) Coolant / Filling (g) R-407c 300g Noise (dB) 65/68 External Output Cooling operation output, alarm output (a non-voltage contact: Resistive load 250V 2A) Display LED RUN LED display / temperature error in the panel Regulatory Compliance Electrical Appliance and Material Safety Law Environmental Response RoHS